A practical guide to configuring Events Table+ so operators can create, update, annotate, and report on PI System event frames from an AVEVA PI Vision display.

Updated August 25, 2026Originally published July 25, 2024Reviewed by Software Athlete PI Vision engineering

Start with the workflow

Why manage event frames in PI Vision?

Event frames give production teams a structured way to describe what happened during a process interval. They can represent a batch, a downtime incident, a quality deviation, or another operational occurrence with a start time, end time, template, and attributes.

Traditional event frame maintenance often requires switching between PI System Explorer, separate tools, and spreadsheets. The Events Table+ custom symbol brings the operational part of that workflow into PI Vision. Users can search for relevant events, add new records, update attributes, and add comments while the display provides the surrounding process context.

Batch monitoring

Capture batch identifiers, operator notes, quality information, and other attributes that help teams compare production runs.

Downtime tracking

Record the reason, duration, impact, and follow-up information needed for root-cause analysis and preventive action.

Events Table+ in PI Vision showing an event frame severity value being edited
Events Table+ keeps event-frame updates close to the operational display context.

Prepare the data model

Set up Events Table+ in PI Vision

The symbol depends on event frame templates and attributes that are already available in the PI System. Define the data model first, then configure the display to search and edit the records your operators need.

Important: static attributes should be designed around the information your team will actually maintain. Typical examples include Batch ID, Operator Notes, Downtime Reason, and Impact Assessment.

1

Open the target PI AF database

In PI System Explorer, open the database that contains the event frame templates used by the process or production area you want to monitor.

2

Create or review the event frame template

Create a template when the workflow does not yet have one, or review the existing template before exposing it in PI Vision. The template defines the event type and its available attributes.

PI System Explorer showing event frame template attributes for Events Table+
Review the template attributes before asking operators to enter or edit them.
3

Add useful static attributes

Define the fields that are not calculated automatically but are important for the workflow, such as batch identity, downtime reason, impact assessment, or operator comments.

4

Add and configure the symbol

Open the target PI Vision display and add Events Table+ from Vision Library+. Configure the event search criteria so the table returns the relevant event frames for the selected context.

Events Table+ custom symbol placed on a PI Vision display
The symbol can be configured as part of an operator-facing PI Vision display.

Operate the workflow

Create, update, and annotate event frames

Once the search criteria are returning the intended records, the table becomes the working surface for event-frame maintenance. Keep edit access aligned with your operating model and make sure users understand which fields are required.

1

Add a new event frame

Use the input fields provided by Events Table+ to enter the required event information, then save the record. The new event frame should become available in the table after the underlying PI System operation completes.

Events Table+ dialog for adding a new event frame in PI Vision
2

Switch to edit mode

To change an existing event frame, set the table to Edit mode and select the record. Confirm that the selected row is the event you intend to modify before changing its time range or attributes.

3

Update the event data

Depending on the attribute data type, the table may present different input controls. Update the basic event information or static attributes, then save the changes and verify the displayed value.

Events Table+ showing an event frame attribute being updated
4

Add operational comments

Use comments to preserve context that is not captured by the structured attributes. A short explanation of the cause, action, or follow-up can make later review much more useful.

Events Table+ comment field for adding operator context to an event frame

Verification habit: after saving, refresh or reapply the search criteria and confirm the event frame appears with the intended time range, template, and attributes.

Turn records into insight

Report and visualize event frames

Event-frame management is most valuable when the resulting records can be reviewed alongside process data and shared with the wider team. The right output depends on whether you need a formal report, a timeline, or a process-context view.

Automated reports

Vision Report+ can turn a PI Vision display into a PDF or image and support scheduled or event-triggered reporting workflows. Use it when event summaries need to reach a distribution list or be stored consistently.

Timeline visualization

Gantt Chart+ provides a timeline-oriented view for comparing event frames across a process or production area.

PI Vision display prepared for conversion to an event frame report
Use a report view when event-frame data needs to be distributed beyond the live display.
PI Vision Gantt Chart+ visualizing event frames on a timeline
A timeline can make overlapping batches, downtime, and production events easier to compare.

For process-context analysis, the Combo Chart+ workflow can help teams overlay event information on process data. Choose the view that matches the question the team is trying to answer.

PI Vision Combo Chart+ showing event annotations over process data

Common questions

Events Table+ FAQ

What must be configured before Events Table+ can be used? +

The relevant PI AF database, event frame template, and attributes must exist and be accessible to the PI Vision workflow. The display then needs search criteria that return the intended events.

Can operators add new event frames from PI Vision? +

Yes, when the symbol is configured for creation and the connected user has the required permissions. The exact fields and controls depend on the event frame template and data types.

Why should static attributes be planned carefully? +

Static attributes are where teams capture context that is not automatically calculated. Clear, purposeful fields improve consistency and make later reporting and analysis more reliable.

How can event frames be shared with people who do not use the live display? +

Use a report-oriented PI Vision display with Vision Report+ for PDF or image output, or use a timeline view such as Gantt Chart+ for event comparison.