Documentation PI Nexus+ Documentation

PI Nexus+ / Reference

PI Adapter Issues and Runtime

This reference lists the PI Adapter statuses, issues and thresholds. The User Guide chapter PI Adapters links here.

Overview

This reference lists the PI Adapter statuses, issues and thresholds. The User Guide chapter PI Adapters links here.

Collector health columns

ColumnGoodWarningErrorNot Evaluated / Unknown
ConfigurationThe adapter's health elements in AF have the attributes, PI Point references and types PI Nexus+ needsNot usedA required monitoring attribute is missing, ambiguous or incompatible, or its PI Point reference is malformed or not foundNot Evaluated: the AF structure is not recognized
Data HealthEvery associated PI Point is healthyAn associated point has a warningAn associated point is badNo point could be associated
RuntimeDevice status Good and heartbeat on timeSee device statuses belowSee device statuses belowUnknown: telemetry unreadable, unbound, bad quality, unrecognized, or monitoring stalled

A PI Point counts toward Data Health only when its OMF data source matches the Collector's data source exactly. Points claimed by two Collectors are shown as ambiguous and left out. Configuration checks are not tracked issues and cannot be suppressed; they are listed under Monitoring setup on the Collector's Issues tab.

Device statuses

Device status published by the adapterRuntime
GoodGood
Starting, ConnectedNoData, NotConfigured, AttemptingFailoverWarning
DeviceInError, Shutdown, RemovedError
Any other valueUnknown

PI Adapter issues

Only Runtime findings become issues. They appear on the Issues page under PI Adapters and on the Collector's Issues tab. The issue type is PI Adapter Runtime Health; the message names the finding.

FindingIssue severityRaised when
Device status WarningWarningThe device status is one of the Warning values
Device status Error or RemovedErrorThe device status is one of the Error values. A Warning that becomes an Error is the same issue, escalated
Heartbeat overdueErrorThe adapter missed its published next-health-message deadline by more than 2 minutes
Telemetry bad quality, unreadable, unbound or unrecognizedWarningThe device status or heartbeat could not be used
Restart loop (service)WarningThe adapter service started 3 or more times within 24 hours. A single restart raises nothing. Counted from the start times stored in the PI archive
Low storage (service)Warning below 10 % free, Error below 5 % freeThe disk the adapter stores its data on is filling up. The adapter buffers on this disk while PI is unreachable

Service issues are raised on the adapter service, appear on every Collector of that service, and do not change a Collector's Runtime. They resolve automatically when the condition clears; a failed or out-of-date read neither raises nor resolves them. CPU use is shown on the Service tab for context and never raises an issue. Data Health and Configuration findings do not become adapter issues; the affected PI Points raise their own issues.

A suppressed Collector sends no runtime email. Runtime emails are set under Admin > Notifications > Delivery Rules > PI Adapter runtime and follow the PI Interface rules: they wait for a confirmation window, repeat an open alert only on escalation, and count a stalled Collector as Unknown.

Thresholds and timings

These are fixed in the product, except the poll interval.

SettingValue
Runtime pollInterface and adapter runtime poll (see Scan Automation in the Administration Guide), default every minute
Monitoring stalledNo successful read for 3 poll intervals and at least 10 minutes; Runtime shows Unknown and the Runtime card counts it as not refreshing
Heartbeat grace2 minutes after the adapter's published deadline
Restart loop3 starts within 24 hours
Low storageWarning below 10 %, Error below 5 % free