Documentation PI Nexus+ Documentation

PI Nexus+ / Reference

PI Point Issues

This reference lists the issues PI Nexus+ raises for PI Points and PointSources, the PI Point health states, and the rule defaults behind them. The User Guide chapters PI Points and Point Sources link here.

Overview

This reference lists the issues PI Nexus+ raises for PI Points and PointSources, the PI Point health states, and the rule defaults behind them. The User Guide chapters PI Points and Point Sources link here.

PI Point health states

StateMeaning
GoodEvery enabled check passed
WarningAt least one finding at Warning severity, none at Error
BadAt least one finding at Error severity
UnknownThe rule checks quality, but the quality could not be determined (Unknown Quality), or the current value could not be read for a new point (Current Value Unavailable)
Not EvaluatedThe point is inventoried, but its rule skips evaluation

A failed value read is not treated as evidence: a point that already has health keeps it until a read succeeds.

The reason shown for Bad or Warning is the first finding in this order: attribute check at Error, bad value, stale, frozen, out of range, attribute check at Warning.

PI Point issues

All appear on the Issues page under the category PI Points (interface mapping issues: see PI Interface Issues and Runtime). Severities marked rule come from the matched PI Point Rule; see PI Point Rule defaults below.

IssueSeverityRaised whenTypical fix
PI Point With No DataRule (default Warning)The current value is the system state No DataCheck the interface or adapter that feeds the point
Uninitialized PI PointRule (default Warning)The current value is Pt Created: the point never received a first valueStart the data flow, or delete an unused point
Bad PI Point ValueRule (default Error)The current value has bad quality. Specific states get their own name: PI Point Collection Timeout (I/O or scan timeout), PI Point Access Denied, PI Point Source Shutdown, PI Point Requires Configuration, PI Point Calculation Failed, PI Point Calculation Disabled, PI Point Scanning Disabled, PI Point Scan State WarningCheck the source device, the interface and the point configuration
Stale PI PointRule (default off)The newest value is older than the rule's stale threshold (default 30 days)Check whether the source still writes; retire the point if not
Frozen PI PointRule (default off)A numeric point (Float16, Float32, Float64, Int16, Int32) keeps receiving values, but none moved beyond the point's exception deviation for the frozen threshold (default 24 hours). Evaluated by health refresh scans and Check health, not by inventory scansCheck the sensor or field signal
PI Point Out of RangeRule (default off)A good numeric value is outside zero to zero + spanCorrect zero and span, or check the instrument
Attribute check name, for example CompressingPer check (default Warning)A PI Point attribute does not meet a check defined in the ruleCorrect the point attribute, or the rule
**Duplicate Source Mapping: PointSource - *InstrumentTag***WarningMore than one active point shares the same PointSource and InstrumentTagRemove or correct the duplicate point
Multiple analysis writersErrorMore than one AF analysis is configured to write to the pointKeep one writing analysis
Conflicting PI Point writersErrorA PI Interface or PI Adapter Collector writes the point, and an AF analysis or the other collector kind also writes itKeep one writer; move the analysis output to its own point

PointSource issue

IssueSeverityRaised whenResolves when
PointSource Without CollectorWarningA PointSource on an archive has active PI Points, and no PI Interface, PI Adapter Collector or inbound External System feeds it, and no purpose is declaredA feeder is found, or an administrator declares a purpose

No warning is raised when the feeder is Feeder unknown: the archive's interface inventory is not available because Interface Tracking is off, has not run or failed.

Fed by values

ValueMeaning
PI Interface / PI AdapterAn interface or Collector claims the PointSource. Both appear during a migration
External SystemEvery point on it belongs to a PI Point Rule linked to an inbound External System
Declared purposeManual / data entry, Analysis outputs, Custom application or Not used
No collectorNothing found; raises PointSource Without Collector
Feeder unknownInterface inventory not available for the archive

PI Point Rule defaults

Set per rule by an administrator (PI Point Rules in the Administration Guide).

CheckEnabled by defaultDefault severityThreshold
InventoryYes
Quality: No DataYesWarning
Quality: Pt CreatedYesWarning
Quality: other bad valuesYesError
StaleNoIgnored30 days
FrozenNoIgnored24 hours
Range (zero/span)NoIgnored
Attribute checksPer checkWarning